Catalyst Monitoring System
Unit of Measure
1 

Item #

Length New

Width NEW

Height NEW

Enclosure

Power Supply (AC)

Environmental Requirements

Weight

Differential Pressure

Inlet Temperature

Additional Description

Quantity
item-1463 N/A 14.75 in N/A 14.50 in N/A 8.00 in N/A NEMA 4 N/A 85 to 264 V N/A LCD must be protected from UV degradation.
Enclosures must be located in an operating environment between 0º and 50ºC (32º to 122ºF).
N/A 16.5 lb N/A (2) 1/8 in NPT N/A (1) 1/2 in NPT N/A
  • Programmable Logic Controller (PLC) which is easy to use with the given tactile keyboard and display screen.
  • Normal operating temperature, pressure drop and tolerances for warning lights set by user providing versatility to each application.
  • Amber warning light to indicate an exhaust inlet temperature or differential pressure which is not yet out of tolerance but should be evaluated as soon as possible. The EPA recommends an inlet temperature between 450º and 1,350ºF and a pressure drop of less than 2 in-H2O due to clogging of catalyst from use.
  • Red warning light to indicate an exhaust inlet temperature or differential pressure which exceeds the maximum or minimum allowable value and should be addressed immediately.
  • High-temperature thermocouple capable of maintaining a minimum tolerance of 5ºF (2.8ºC).
  • Option of mounting differential pressure transmitter on left or right side of enclosure for convenient application to existing or new systems.
  • 2 GB microSD memory card capable of recording years of logged data.
  • Customizable recording interval based on application requirements. For RICE NESHAP applications, 15 minute interval between recordings is required which is far surpassed by default settings.